Waveform Correlation Based Harmonic Voltage Contribution Determination of Iron and Steel Plants Supplied From PCC

Özgül SALOR-DURNA

In this research work, a new method which determines the individual harmonic voltage contributions of the EAF plants supplied from a point of common coupling (PCC) to the PCC voltage is presented. EAFs are one of the most significant sources of the harmonics, especially the uncharacteristic ones, therefore it is important to be able to discriminate the amount of individual contributions from the feeders of a PCC supplying multiple EAFs. The proposed method uses the relationship derived between the correlation coefficient of the PCC voltage and the feeder current waveforms and the harmonic volt ...More

Access to Files

Waveform Correlation Based Harmonic Voltage Contribution Determination of Iron and Steel Plants Supplied From PCC

Özgül SALOR-DURNA

This paper presents a new waveform correlation based method which determines the individual harmonic voltage contributions of Electric Arc Furnace (EAF) plants supplied from a point of common coupling (PCC). The method is based on the waveform correlation computations between the PCC voltage and the feeder current at the individual harmonic frequency. PCCs supplying multiple EAF plants usually suffer from high voltage harmonic components due to their operation principles. A relationship between the correlation coefficient of the PCC voltage and the feeder current waveforms, and the harmonic vo ...More

Access to Files

Harmonic Contribution Detection of Iron and Steel Plants Based on Correlation of Time-Synchronized Current and Voltage Signals

Özgül SALOR-DURNA

In this paper, the problem of detecting the harmonic responsibility of iron and steel (I&S) plants, which are supplied from a point of common coupling (PCC) is addressed. A new harmonic responsibility measure, which does not require the instantaneous impedance measurements, is proposed to present the amount of harmonic responsibility of each plant supplied from the PCC. The algorithm is based primarily on the correlation of voltage and current signals which are measured with a time-synchronized manner at the PCC. The proposed method is first verified using both synthetic data generated in PSCA ...More

Access to Files

Harmonic Contribution Detection of Iron and Steel Plants Based on Correlation of Time-Synchronized Current and Voltage Signals

Özgül SALOR-DURNA

In this research work, a new harmonic responsibility measure is proposed to extract the amount of harmonic responsibility of each plant supplied from the point of common coupling (PCC). The proposed method uses a function of the correlation coefficients between the voltage and current signals measured synchronously at the PCC. After the verification of the method on synthetic data generated in simulation environment, field data measurements of voltage and current are used to test the practicability of the proposed method. Harmonic contributions of the iron and steel (I&S) plants obtained using ...More