In this research work, a new method which determines the individual harmonic voltage contributions of the EAF plants supplied from a point of common coupling (PCC) to the PCC voltage is presented. EAFs are one of the most significant sources of the harmonics, especially the uncharacteristic ones, therefore it is important to be able to discriminate the amount of individual contributions from the feeders of a PCC supplying multiple EAFs. The proposed method uses the relationship derived between the correlation coefficient of the PCC voltage and the feeder current waveforms and the harmonic volt ...Более
In this paper, the problem of detecting the harmonic responsibility of iron and steel (I&S) plants, which are supplied from a point of common coupling (PCC) is addressed. A new harmonic responsibility measure, which does not require the instantaneous impedance measurements, is proposed to present the amount of harmonic responsibility of each plant supplied from the PCC. The algorithm is based primarily on the correlation of voltage and current signals which are measured with a time-synchronized manner at the PCC. The proposed method is first verified using both synthetic data generated in PSCA ...Более